GO
SEARCH:

WeatherKing Heat Pump Won't Turn on

The part(s) or condition(s) listed below for the symptom Heat pump won't turn on are ordered from most likely to least likely to occur. Check or test each item, starting with the items at the top of the page.

Most Frequent Causes for Heat pump won't turn on

For the most accurate results, enter your model number.


Cause 1Run Capacitor

A run capacitor stores and releases a charge to start and run the condenser fan motor. If the capacitor is defective, the fan motor might be noisy, overheat, or not run at all. To determine if the run capacitor has failed, inspect the capacitor. If the dual run capacitor is bulging or leaking, replace it.

Parts
Cause 2Capacitor

A capacitor stores and releases a charge to start and run the condenser fan motor. If the capacitor is defective, the fan motor might be noisy, overheat, or not run at all. To determine if the capacitor has failed, inspect the capacitor. If the dual run capacitor is bulging or leaking, replace it.

Parts
Cause 3Dual Run Capacitor

A dual run capacitor stores and releases a charge to start and run both the compressor and the condenser fan motor. If the capacitor is defective, the fan motor might be noisy, overheat, or not run at all. To determine if the dual run capacitor has failed, inspect the capacitor. If the dual run capacitor is bulging or leaking, replace it.

Parts
Cause 4Condenser Fan Motor

To determine if the condenser motor is working, use a multimeter to test the incoming voltage to the motor. If the condenser fan motor is receiving the correct voltage but the motor still won’t run, inspect the capacitor to ensure that it is not at fault. If the capacitor is not bulging or leaking, replace the condenser fan motor.

Parts
Cause 5Fan Motor

To determine if the fan motor is working, use a multimeter to test the incoming voltage to the motor. If the fan motor is receiving the correct voltage but the motor still won’t run, inspect the capacitor to ensure that it is not at fault. If the capacitor is not bulging or leaking, replace the fan motor.

Parts
Cause 6Wall Thermostat

The control board sends a low voltage signal of 24 volts to the contactor through the wall thermostat. When the contactor receives the signal from the control board, it closes the circuit, sending voltage to the outside unit components. There should be 24 volts between the common (“C”) and yellow (“Y”), and common ("C") and orange ("O") thermostat wire terminals on the air handler control board when the wall thermostat is in the heating mode. You can check for this voltage with a multimeter. If voltage is not reaching the contactor or reversing valve, it's likely the wall thermostat is defective and will need to be replaced.

Parts
Cause 7Wifi Thermostat

The control board sends a low voltage signal of 24 volts to the contactor through the WiFi thermostat. When the contactor receives the signal from the control board, it closes the circuit, sending voltage to the outside unit components. There should be 24 volts between the common (“C”) and yellow (“Y”), and common ("C") and orange ("O") thermostat wire terminals on the air handler control board when the WiFi thermostat is in the heating mode. You can check for this voltage with a multimeter. If voltage is not reaching the contactor or reversing valve, it's likely the WiFi thermostat is defective and will need to be replaced.

Parts
Cause 8Contactor

The furnace or air handler control board sends a low voltage signal to the contactor. When the contactor receives the signal from the control board, it closes the circuit, sending voltage to the outside unit components. If the contactor is defective, it will not provide voltage to the outside unit. To determine if the contactor is at fault, use a multimeter to test the contactor for continuity. If the contactor does not have continuity, replace it.

Parts
Cause 9Control Board

If the heat pump unit contactor is not receiving 24 volts or power is not getting to the inside blower motor, a possible cause is a defective heat pump control board. While this is not a common problem, if all other potentially faulty components are working properly, the control board should be replaced.

Parts
Cause 10Compressor

The compressor is a pump which compresses the refrigerant and circulates the refrigerant through the evaporator and condenser coils. If the compressor is not working, the heat pump won't turn on. However, this isn’t usually the case. Before replacing the compressor, first check all of the more commonly defective components. If all of the other components are working properly, use a multimeter to test the compressor for continuity. If there is an open circuit, the compressor is likely defective. If the compressor is defective, it must be replaced by a licensed technician.

Parts
Cause 11Incoming Power Problem

The central air condensing unit is energized with 240 volts of electricity. This electricity then flows through the disconnect box to the compressor and condenser fan motor. The disconnect box enables the air conditioning unit to be turned off outside. The disconnect box includes a cartridge which may contain fuses. If the compressor and condenser fan motor do not run, the disconnect box fuses may have blown, or the circuit breaker supply power to the disconnect box may have tripped. To determine if the disconnect box fuses have blown, use a multimeter to test the fuses for continuity. If the fuses do not have continuity, replace the disconnect box.

Cause 12Check Fault Codes

If the furnace or air handler stops working properly, the control board will often display a fault code to help diagnose the problem. The fault codes are displayed by a steady or flashing light on the control board. The light indicates either an error code or the status of the furnace or air handler. Some manufacturers will use red and green lights to indicate specific fault codes. Fault code descriptions are often displayed on the access cover of the unit for easy reference.

Cause 13No Power to Furnace or Air Handler

The furnace or air handler needs to have power reaching it for the heat pump unit to run. If the furnace or air handler control board has an indicator light, confirm the light is illuminated which indicates power is present. If there is no power to the furnace or air handler, check the home's circuit breaker or fuse. Confirm the power switch on the side of the furnace or air handler is turned on.

Cause 14Transformer

The control board sends a low voltage signal of 24 volts to the contactor. When the contactor receives the signal from the control board, it closes the circuit, sending voltage to the outside unit components. Some air handlers have a separate transformer for the 24 volt circuit, so if the contactor is not receiving the proper voltage, it's likely this transformer has failed and the component will need to be replaced.

Parts
Cause 15Thermostat Not Set Properly

For the heat pump to work properly, the wall thermostat should be set for "Cool" or "Heat" and the fan set for "Auto" or "Fan On". The temperature setting also needs to be set properly. When the thermostat is set properly, both the outdoor unit and the furnace or air handler blower should be running.

Cause 16Wall Thermostat Batteries

Most wall thermostats are either powered by an enclosed battery or by the furnace or air handler transformer. If the thermostat display is dead, you can remove the thermostat cover and look for replaceable batteries. Replace the batteries if needed and check operation.