GO
SEARCH:

Luxaire Furnace Burners Won’t Stay Lit

The part(s) or condition(s) listed below for the symptom Furnace burners won’t stay lit are ordered from most likely to least likely to occur. Check or test each item, starting with the items at the top of the page.

Most Frequent Causes for Furnace burners won’t stay lit

For the most accurate results, enter your model number.


Cause 1Gas Supply Problem

Check the gas control valve to ensure that it is turned on and there is gas present at the valve. Natural gas pressure should be close to 4 inches water column at the furnace input; propane pressure close to 11 inches water column at the furnace input. The gas pressure can be checked with a manometer at the valve. Low gas pressure can cause a weak flames and inconsistant lighting.

Cause 2Control Board

Control Board

Parts
Cause 3Clogged or Restricted Vent Pipe or Heat Exchanger

If the flame rollout limit switch is tripping a restricted or cracked heat exchanger, or restricted outlet pipe, could be preventing the flame from being drawn through the heat exchanger properly. This can be very dangerous and the furnace should be inspected by a qualified service technician. You should never keep resetting the rollout limit without fixing the problem. If the heat exchanger is cracked, carbon monoxide can enter the home's venting system causing death. It is recommended to have at least one carbon monoxide detector on each floor of the home.

Cause 4Igniter

Igniter

Parts
Cause 5Improper Vacuum or Pressure

The draft inducer fan motor assembly creates a vacuum when running which closes the pressure switch. Check the pressure hose and port on the inducer assembly for leaks or obstructions. A clogged condensate trap or drain, or restricted heat exchanger, can also cause a pressure switch to not function. Replace the pressure switch if there is proper vacuum or pressure but the switch is not working properly. You can test the pressure switch for electrical continuity with a multimeter. The contacts will either close or open depending on the application.

Cause 6Flame Sensor

Flame Sensor

Parts
Cause 7Pressure Switch

Pressure Switch

Parts
Cause 8Hose

Hose

Parts
Cause 9Tube

Tube

Parts
Cause 10Air Flow Problem

The furnace has two seperate requirements for air flow. The homes air is heated and recirculated through the heat exchanger and heat ducts through an air filter. A clogged air filter can cause the furnace to overheat and shut down, and should be replaced at least twice a year depending on the type of filter and environment. The furnace must also have proper airflow through the burner and heat exchanger in order to continue running. The furnace draws air from the surrounding area or from outside the room. If the furnace is located in a utility closet or in a cramped storage room, there may not be sufficient available air for the furnace to heat properly. If the furnace draws air from outside the home, check for an obstructions at the air inlet.

Cause 11Draft Inducer Motor

Draft Inducer Motor

Parts
Cause 12Draft Inducer Motor Assembly

Draft Inducer Motor Assembly

Parts